Six-monthly testing is central to emergency lighting compliance in Perth. In Class 2-9 buildings, emergency and exit lighting testing in Perth includes inspecting the fittings and testing their battery operation every six months.
It’s easy to assume exit signs and emergency lights only need attention when a fault is obvious. But a fitting can look normal and still fail to provide light for long enough during a power outage. Routine testing helps ensure the system is ready to support safe evacuation.
This article explains which Perth premises need emergency lighting, what to record in a maintenance logbook and what happens during a six-monthly discharge test. It also covers when building changes or faults call for further attention, and how checks and records help keep emergency lighting ready when normal power is interrupted.
Key Takeaways
- Find out which building types need emergency and exit lighting, and how AS/NZS 2293 informs their maintenance.
- Learn what to record in an emergency lighting logbook so test results, faults and repairs are traceable.
- Understand what six-monthly discharge testing checks and how long fittings must operate on battery power.
- See when building changes, faults or urgent electrical issues call for professional attention.
Who Needs Emergency Light Testing in Perth?
In Western Australia, emergency lighting requirements apply to relevant buildings and workplaces, not just large businesses. The National Construction Code and AS/NZS 2293 set out which buildings and areas need emergency and exit lighting.
Emergency Lighting Requirements
Emergency lighting requirements cover the provision, design and maintenance of lights that help people leave safely during a power failure. They matter to small businesses because the size and use of a premises can affect whether lighting is required. A Perth shop or office larger than 100 square metres is likely to need emergency lighting. AS/NZS 2293.1 covers system design, installation and operation, while AS/NZS 2293.2:2019 governs routine service and maintenance in Western Australia. AS/NZS 2293.3 covers emergency escape luminaires and exit signs.
Buildings and Workplaces Requiring Testing
The National Construction Code requires emergency and exit lighting in Class 2-9 buildings, including relevant commercial and public premises. The required coverage depends on the building and its areas, including the paths people need to use to leave. This matters in workplaces where a power failure could leave an exit route dark. A changed layout can also affect whether existing lights cover escape routes adequately.
In Western Australia, the Health (Public Buildings) Regulations 1993 require illuminated exit signs in public buildings to be installed and maintained in accordance with Australian Standard 2293. The Work Health and Safety Act 2020 provides the workplace safety framework. Together with AS/NZS 2293.2, these requirements mean relevant emergency lights and exit signs need inspection and maintenance, not just installation.
There is no single penalty amount for every emergency lighting failure. Consequences depend on the breach and circumstances, and inadequate lighting can create liability if it compromises safe evacuation.
If a fitting fails, arrange to repair or replace it, then test it again. Record the fault and repair to keep a clear maintenance history. A working exit sign does not confirm that nearby emergency lights will operate on battery power during an outage.
Do I need maintenance records or a logbook for emergency lighting?
Yes. Record emergency-lighting test results, faults and repairs in a logbook or digital register. Clear records help workplace managers and owners track maintenance and demonstrate the system’s service history. Records of emergency and exit lighting testing in Perth also make faults and repairs easier to trace.
Testing and Maintenance Records
Testing and maintenance records document what was checked, what failed and what electrical work followed. Each logbook entry should include the test date, the result for each luminaire and the technician’s licence number. Record faults and repairs as well, so a failed fitting can be traced from discovery through to corrective work. AS/NZS 2293.2 covers routine service and maintenance of emergency lighting systems.
Organise entries by fitting or location, such as a stairwell exit sign or a luminaire along an escape route. This makes recurring faults easier to spot and helps show whether repairs resolved them. A blank entry or a general note that “lights passed” does not record the result for each luminaire. Preserve a continuous audit trail of tests and maintenance for seven years. Complete emergency and exit lighting testing records in Perth help show how issues were resolved.
Logbooks and Digital Compliance Records
A logbook can be kept on paper or as a digital register, as long as it captures test results, faults and repairs. Digital records can help managers retrieve a specific entry without searching through paper files. Keep records accessible to those responsible for workplace checks, and organise entries by date and fitting.
Automatic monitoring does not replace regular inspections, repairs when faults are reported or properly maintained records. Monitoring can flag a fault, but the register should also show what happened next. Record the fault, repair and later test result for the affected fitting to create a clearer audit trail than monitoring alerts alone.
Use the register to track outstanding faults through to repair and retesting. If checks uncover an electrical issue, arrange the required Perth electrical services and document the outcome.
Six-monthly emergency light discharge testing
Emergency lights and exit signs need inspection and discharge testing every six months. Each fitting must operate on battery power for at least 90 minutes during subsequent tests.
Six-monthly Inspection and Testing
A six-monthly inspection checks the fittings and confirms they illuminate when normal power is interrupted. It matters because a light that works on mains power may still have a depleted battery. Before a discharge test, the normal power supply must have been uninterrupted for at least 16 hours.
During a discharge test, normal power is simulated as failed, each fitting is checked and the results are recorded. Commercial premises can schedule testing outside busy hours to allow batteries to recharge afterwards. This helps limit disruption while escape routes are checked.
Full-duration Discharge Tests
A full-duration discharge test measures how long each emergency fitting stays illuminated on battery power. In Western Australia, local guidance states that new batteries should keep emergency lights and exit signs illuminated for at least two hours. Subsequent discharge tests require at least 90 minutes of operation.
An annual inspection is also recommended. It includes reviewing the system and cleaning light-emitting and reflecting surfaces. Six-monthly discharge tests assess battery operation, while the annual inspection adds a broader maintenance check. Keeping these activities distinct makes the schedule easier to follow.
A fitting that dims or fails after 85 minutes of a 90-minute test fails the required duration. Record the result and arrange repair or replacement of the faulty fitting. After batteries are replaced, conduct a two-hour discharge test. Testing confirms whether the fitting can provide illumination for evacuation, rather than merely lighting up at the start.

Emergency lighting services in Perth and WA
Emergency lighting must operate when a power failure interrupts normal lighting, helping occupants leave safely. In Perth, monthly visual inspections and an annual full inspection help identify damage, obstructions or changes that may affect the system.
Comparing Testing Providers
Compare the inspection scope, how each fitting is tested, and whether faults and repairs are recorded. A switch test alone does not establish whether a battery can sustain illumination. A clear scope should cover exit signs, emergency fittings and escape-route lighting. Building managers should also consider whether recent layout changes call for a coverage review.
Exit signs are intended to remain illuminated during normal operation. Ask for the test results and identified faults to be documented, so the building’s maintenance history reflects what was checked and what happened next.
Qualified Lighting Testers
Emergency lighting maintenance in public buildings must be carried out by a suitably qualified and experienced person. Because testing and repair involve electrical work, a licensed electrician is the appropriate professional for faults requiring electrical attention. Business owners cannot legally certify their own system unless they are licensed electrical contractors.
This distinction matters when a test shows that a fitting has failed: recording the fault does not fix it. Arrange an appropriate repair, then test the fitting and document the result. Batteries and fittings can degrade over time, so a fitting that lights during a visual check may not last for the required duration.
Review emergency lighting coverage after a building layout change, particularly if partitions or altered routes affect how people move during an evacuation. Monthly visual inspections can reveal visible damage, while the annual inspection provides a broader maintenance review. Together, these checks help identify issues between discharge tests and keep records aligned with the building’s current layout.
For electrical support with a lighting fault or building change, discuss emergency lighting electrical work.
Banner Power: 24/7 Emergency Electrical Services
Banner Power provides 24/7 Emergency Electrical Services for urgent power issues and critical electrical failures. If an emergency lighting fault is linked to a wider electrical problem, Banner Power’s Commercial Electrical Services can support commercial premises, while its Residential Electrical Services and Industrial Electrical Solutions serve other property and site needs.
For routine maintenance, keep the six-monthly testing schedule and records up to date. If a fitting fails or an urgent electrical issue affects the building, arrange appropriate electrical support to address the fault and document the outcome.
Contact Banner Power to discuss electrical support for your premises.
Keep your lighting plan current
Building use can change over time. A new tenancy, internal partition or altered exit route may affect how people move through a premises during a power failure. Include emergency lighting reviews in plans for these changes so the system remains aligned with current escape routes.
For Perth premises, regular emergency and exit lighting testing is one part of a considered electrical maintenance plan. Banner Power’s Commercial Electrical Services, Residential Electrical Services and Industrial Electrical Solutions support electrical needs across different property types. Where a fault needs attention or a change affects electrical infrastructure, a clear record of the issue helps inform the next discussion.
Take the next step by discussing your premises’ electrical needs with Contact Banner Power. A well-maintained plan helps keep safety considerations in view as your building evolves.
Frequently Asked Questions
How much does an emergency light test cost?
The cost depends on the premises and work involved, and is outlined in a quotation. Factors include the number and location of fittings, access arrangements, the testing required and whether faults need repair. Testing and corrective electrical work are separate tasks, so the scope affects the quotation. When requesting a quote for a Perth site, share its layout and any known lighting faults.
How often do emergency exit lights need to be tested?
Emergency lights and exit signs need inspection and discharge testing every six months. This schedule covers battery-backed operation, not just a quick check that a fitting appears illuminated. A separate annual inspection is recommended for a broader review, including cleaning light-emitting and reflecting surfaces. Keeping these tasks distinct helps premises managers plan routine testing and wider maintenance without treating one as a substitute for the other.
Do exit signs need to stay illuminated?
Yes. Exit signs are intended to remain illuminated continuously, 24 hours a day, 365 days a year. A sign that is dark during ordinary operation may not clearly identify an exit before a power failure occurs. For example, if a sign is switched off during a building’s normal operating hours, it may not provide continuous direction to occupants. Include normal illumination in visual checks, as well as battery operation during scheduled tests.
Do small shops and offices in Perth need exit signs?
It depends on the building’s class, use and required escape routes. A Perth shop or office larger than 100 square metres is likely to need emergency lighting, but that threshold alone doesn’t establish every exit-sign requirement. The National Construction Code identifies Class 2-9 buildings as requiring emergency and exit lighting. For a small premises, consider its building classification and whether occupants need illuminated directions along escape routes.
How long must exit luminaires stay on during a power outage?
During subsequent discharge tests, emergency lights and exit signs must stay illuminated on battery power for at least 90 minutes. Western Australian local guidance says new batteries should provide at least two hours of illumination. These figures describe different stages: the new-battery expectation and the required duration during subsequent tests. If a sign goes dark during an outage, treat it as a fault requiring attention, rather than relying on its normal mains illumination.
How long should emergency lights stay on during battery operation?
For subsequent discharge tests, each emergency-light fitting must operate on battery power for at least 90 minutes. New batteries are expected to keep emergency lights and exit signs illuminated for at least two hours under Western Australian local guidance. The distinction matters when interpreting a test result: the 90-minute requirement applies to subsequent tests, while the two-hour duration describes new batteries. Record each fitting’s result separately so a weak unit isn’t hidden by others passing.